What are the daily maintenance and maintenance methods of the air shower room?
Daily maintenance and maintenance methods of air shower room
A, daily maintenance (per shift/every day)
Clean internal and external surfaces
Wipe the door, inner wall, nozzle and bottom plate with neutral cleaner, without dust, oil and water stains.
Food workshop focus: no water, no mold, no odor.
Check the door and interlock function.
Double doors should be able to close normally, but not open at the same time (stop immediately for repair if interlock fails).
Door seal is intact, without deformation and air leakage.
Check the fan and shower effect.
Start the air shower and listen to the sound of the fan: no abnormal noise or vibration.
Feel that the air from each nozzle is even and powerful, and there is no wind blockage or deviation.
Clean the floor/air return.
Clean up the sundries, hairs and dust at the bottom to prevent the return air passage from being blocked.
Check the filter screen of the air return port in each shift, and clean up the dirt in time.
Check lighting and emergency stop
Lighting is in good condition; The emergency stop button functions normally.
Second, weekly maintenance
Cleaning the primary filter
Take out the primary filter, clean it with clean water/neutral detergent, dry it and put it back.
Replace it directly if it is deformed, damaged or blocked seriously.
Clean the nozzle completely.
Wipe/clean the nozzle hole to ensure no dust or blockage.
Check the circuit and wiring.
Check the wiring for looseness, fever and peculiar smell. It is forbidden to operate the electric cabinet with wet hands.
Third, monthly maintenance
Check the high efficiency filter (HEPA)
Observe the wind: the wind power is obviously smaller, the blowing time is longer, and the pressure difference in the workshop is lower, indicating that the resistance of the high efficiency filter is larger.
Conditional differential pressure gauge can be used to judge, and it will be replaced if it exceeds the standard.
Lubrication of door shaft and hinge
Give a small amount of lubricating oil to the hinge and door shaft, and the switch will be smooth and sound-free.
Check the induction/control system
Infrared sensing, automatic door closing and shower timing functions are normal.
Fourth, quarterly/semi-annual maintenance
Replace the primary filter
After cleaning for many times, it becomes thinner, deformed and leaks dust, and it is directly replaced with a new one.
Replace the high efficiency filter
The food cleaning workshop is generally replaced once every 6 to 12 months (depending on the amount of environmental dust).
Leak detection/sealing is required after replacement, and no air leakage is allowed.
Overall performance check
Wind speed, interlock, door sealing, grounding and circuit safety shall be thoroughly checked once.
Five, food workshop special precautions
It is forbidden to use strong acidic and alkaline cleaners to avoid corrosion of the box and sealing strip.
Keep the air shower room dry and ventilated to prevent mold growth.
It is forbidden to bring water, oil and dirt into the shower room.
Stop using it immediately and report for repair in the following situations:
Interlocking failure
Abnormal sound and large vibration of the fan
There is no wind at all or the wind is extremely weak
The door is deformed and cannot be closed tightly.
The circuit is hot and burnt.
Six, minimalist summary (can be posted on the wall)
Daily: clean, check the door, check the wind and clean the filter screen.
Weekly: initial washing effect and nozzle opening.
Monthly: Check the efficient and lubricated door shaft.
Quarterly: change filter materials and do security inspection.